NORMAL STANDBY - Screen displays SYSTEM STATUS: NORMAL with the time and date.
POWER - Power LED glows steady green to indicate that the AC power is on; blinks when the System is on battery backup.
PARTIAL SYSTEM DISABLED - Partial System Disabled glows steady yellow when any device is disabled.
LAMP TEST - Press the Menu button. Next, press the button below Lamp Test at the bottom of the screen. The Lamp Test begins and will run for 30
seconds. (You can exit the Lamp Test at any time by pressing the Menu button.)
Follow these steps if there is an event. (The sequence is the same for all types of events):
Appropriate LED blinks (ALARM: red, SUPERVISORY: yellow, SECURITY: yellow, TROUBLE: yellow) An internal audible alarm sounds steady when
there is an unacknowledged fire alarm. It pulses if all alarms are acknowledged, but there is at least one supervisory, trouble or security condition.
Highest priority events tab displays with the total number of events and two lines of detail for each event. All UNACKNOWLEDGED events will
have a blinking ! preceeding each event in the list. Display other event types by pressing appropriate lit button at top of screen.
Audibles ON will glow steady yellow (ALARM only) Buttons light in sequence to focus on the next logical operation. Press lit button at bottom of
screen:
Acknowledge Event - Press to acknowledge the active event (! will change to ü and apropriate LED will glow steady.)
Silence Audibles - Press to silence audibles. (Audibles SILENCED glows - ALARM only)
WARNING: The Control-Arm/Disarm feature must not be used to silence alarm-sounding appliances.
Unsilence Audibles - Press to unsilence audibles. (Audibles ON glows - ALARM only)
Reset System - Press to reset the system.
More Info - Press button to display the following 4 tabs at bottom of screen:
Details
Alarm Location - Description of the event area
Event Info - Number of devices involved in reporting the event
Alarm Types - List of the types of devices involved in the event
Emergency Contact - Name and Phone Number of office contact person
Fire Service Equipment In The Area - Displays up to 6 icons
Hazards/People In The Area - Displays up to 6 icons
Map - Displays a map of the event area as programmed in the Zeus tool
Devices - Displays a description of each device involved in the event
Back - Returns to appropriate event list display
More
Info
SECURITY
ALARM
SUPERVISORY
TROUBLE
SILENCED
PARTIAL SYSTEM
DISABLED
AUDIBLES
ON
POWER
?
+
....
Scroll UP through
the list of events
Menu
When lit, provides
more information on
the highlighted event.
Go back to previous screen.
Scroll DOWN through
the list of events
Context sensitive help.
Alarms #
FIRE ALARM LIST
Supers #
Securitys #
Troubles #
Device custom message
10:53
!
Device custom message
Event Category
Event Category
11:00
(Currently not used)
Device custom message
10:57
(Currently not used)
4
4
4
4
Device custom message
Event Category
11:03
(Currently not used)
Device custom message
Event Category
Acknowledge
Alarms
Silence
Audibles
Unsilence
Audibles
Reset
System
11:06
(Currently not used)
(Currently not used)
_
Siemens Building Technologies
Fire Safety
Operating Instructions
Model: FireFinder-XLS
These instructions should be framed and located adjacent to the control unit for ready reference.
MAINTENANCE
If the system is connected to the fire department, etc., or actuates an internal system, disarm the appropriate outputs before servicing to prevent
actuation. (See the FireFinder-XLS Manual, P/N 315-033744 for procedures.) Notify personnel at your facility that a System test is being performed so
that any alarm sounding can be ignored during the test. Notify the fire department before resetting the system. We recommend the following
inspection and testing schedule:
Every Six Months
1. Check the sensitivity of each detector, using the Report - Status - Sensitivities menu.
2. Check that all appropriate detectors are armed, using the Maint - Control - Arm/Disarm menu.
3. Activate a detector or alarm-initiating device. To test for Go-No Go operation, use Test Gas, P/N 315-282747, following the instructions on the
label. Check that the detector LED lights and the proper indication is given at the Control Panel.
4. Verify that an alarm can be acknowledged and that the System can be silenced and reset.
5. Verify the time and date setting of the System clock.
Every Year
1. Check that the output logic functions work in accordance with customer specifications.
2. Perform any other test required by national or local fire codes.
NOTE:
Canadian installations require a 10-event display. In the Zeus Programming tool, set the country code to Canada to enable the 10-event display mode.
VOICE EVACUATION
1 Press Acknowledge Alarms (See
in illustration to the left).
2. Press Silence Audibles to silence all the alarms (See
in illustration to the left).
3. Press the specified button on the LVM/SCM to perform the following operations:
ALL PAGE - to page all speaker zones
SELECT PAGE - to select individual speaker zones to page
ALL EVAC 1 OR 2 - to activate all speaker zones to receive the EVAC 1 or 2 signal
SELECT EVAC 1 OR 2 - to select individual zones to receive the EVAC 1 or 2 signal
ALL ALERT 1 OR 2 - to activate all speaker zones to receive the ALERT 1 or 2 signal
SELECT ALERT 1 OR 2 - to select individual zones to receive the ALERT 1 or 2 signal
ALL CONVENIENCE PAGE - to convenience page all speaker zones
SELECT CONVENIENCE PAGE - to select individual speaker zones to conveiencepage
ALL BACKGROUND MUSIC - to play background music in all speaker zones
SELECT BACKGROUND MUSIC -- to select individual speakers zones to play background music
USING THE MICROPHONE
Remove microphone from holder. Select the zones for paging (see #3 above), then press and hold key switch on microphone. When pre-announce
tone ends and Ready To Page LED lights, continue holding key switch and speak into the microphone.
To discontinue a paging operation, release the microphone keyswitch for more than 5 seconds. All zone lights begin to flash green and the speaker
zones shut off. If you release the keyswitch for less than 5 seconds, the paging operation does not discontinue.
The page function automatically cancels after 2 minutes of inactivity.
USING THE TELEPHONE
A telephone call-in is indicated on the SCM with a steady tone and a flashing LED at the remote telephones zone button.
Press the zone button to talk (multiple lines may be active simultaneously). Press the button again to deselect the zone.
Use either the master telephone or a remote telephone to page. The microphone always overrides a remote telephone (Wardens Page).
To page from the master telephone:
1. Press the button for the page category that applies: ALL PAGE, SELECT PAGE, PAGE TO EVAC, PAGE TO ALERT, or PAGE TO OTHER.
2. If applicable, press zone buttons to select the zone to be paged.
3. Press PHONE PAGE.
4. Pick up phone handset and speak when the Ready To Page LED glows.
To page from a remote telephone (Wardens Page):
1. When a person takes the remote telephone off-hook, the Call-In audible sounds at the command console.
2. At the command console press the zones selection button to enable the remote telephone to make a page.
3. Press the button for the page category that applies: ALL PAGE, SELECT PAGE, PAGE TO EVAC, PAGE TO ALERT or, PAGE TO OTHER.
4. If applicable, press zone buttons to select the zones to be paged.
5. Press WARDENS PAGE.
6. The person at the remote telephone presses the Push-To-Talk button on the telephone and speaks.